LTSWITCH GEAR PANELS

MV Panel

MV Panel Type Freestanding cubicle compartmentalized – Form 4
Sheet Steel 16 SWG / 1.6 mm CRCA for enclosure outer shell
14 SWG / 2.0 mm CRCA for panel doors
Surface finish Pretreated 7-tank process
Powder coated or spray painted – polyurethane
Bus bar supports SMC/DMC insulators
Partition 3.2 mm FRP sheet
Shrouding 1.6 mm FRP sheet
Incomer Up to 3200 A, TPN/4P Air circuit breaker – 65 kA
Out going As per customer requirement – Fuse switch unit or MCCB -35 kA
Interlocking 2 lock + 1 key

TOP


Sub Switch Board

Sub Switch Board

Sub Switch Board Type Freestanding cubicle compartmentalized – Form 4
Sheet Steel 16 SWG / 1.6 mm CRCA for enclosure outer shell
14 SWG / 2.0 mm CRCA for panel doors
Surface finish Pretreated 7-tank process
Powder coated or spray painted – polyurethane
Bus bar supports SMC/DMC insulators
Partition 3.2 mm FRP sheet
Shrouding 1.6 mm FRP sheet
Incomer Up to 800 A, TPN, Fuse switch unit or MCCB– 35 kA
Out going As per customer requirement – Fuse switch unit or MCCB -25 kA

TOP


Motor Control Center – Option I

Motor Control Center

Motor Control Center Type Freestanding cubicle compartmentalized – Form 4
Sheet Steel 16 SWG / 1.6 mm CRCA for enclosure outer shell
14 SWG / 2.0 mm CRCA for panel doors
Surface finish Pretreated 7-tank process
Powder coated or spray painted – polyurethane
Bus bar supports SMC/DMC insulators
Partition 3.2 mm FRP sheet
Shrouding 1.6 mm FRP sheet
Incomer Up to 800A, TPN, Fuse switch unit or MCCB– 35 kA
Out going As per customer requirement – Fuse switch unit or MCCB -25 kA as incomer for individual starter OR
Motor protection circuit breakers – 50 / 100 kA
Controls Illuminated push buttons with LED for on and off
Indications – LED pilot lamps for power on, motor on and trip.

TOP

Motor Control Center – Option II

Motor Control Center

Type Desk type Console – Form – 1/2
Sheet Steel 16 SWG / 1.6 mm CRCA for enclosure outer shell
14 SWG / 2.0 mm CRCA for panel doors
Surface finish Pretreated 7-tank process
Powder coated or spray painted – polyurethane
Bus bar supports SMC/DMC insulators
Partition 3.2 mm FRP sheet
Shrouding 1.6 mm FRP sheet
Incomer Up to 400 A, TPN, Fuse switch unit or MCCB– 35 kA
Out going As per customer requirement – Fuse switch unit or MCCB -25 kA as incomer for individual starter OR
Motor protection circuit breakers – 50 / 100 kA

Controls Illuminated push buttons with LED for on and off
Indications – LED pilot lamps for power on, motor on and trip

TOP


Fuse Distribution Boards

Fuse Distribution Boards

TOP


Automatic Power Factor Correction Panel

Automatic Power Factor Correction Panel


Go Top

 

© Copyright All Right Reserved hitec system Site Designed by Nissi Infotech